Elevator machine room ventilation requirements.
The mechanical engineer s design that relates to the elevator system and ventilation requirements for the machine room and elevator hoistways are a key to the safe and efficient operation of a building system.
Of the total required vent area not less.
Such vents shall comply with the following requirements.
3003 2 fire fighters emergency operation.
A where mechanical ventilation equipment is provided it shall be located outside the elevator machine room where possible.
Ventilation rates for storge room 0 12 cfm ft2 0 cfm person electrical equipment rooms 0 06 cfm ft2 0 cfm person and elevator machine rooms 0 12 cfm ft2 0 cfm person are are now included in table 6 1 62 1 2007 whereas 62 1 2004 did not include these spaces in table 6 1.
Traction elevator machine room.
The ma board of elevator regulations has removed the longstanding amendment to asme a17 1.
By the elevator or in the hoistway or in an elevator machine room or a control space or a control room see 2 27 3 2 shall initiate phase i emergency recall operation.
Safety code for elevators and escalators requiring a means of elevator ventilation to the outer air from enclosed elevator hoistways and machine rooms.
Anyone using the room should have enough room to remove replace inspect and maintain elevator equipment.
The international codes i codes are the widely accepted comprehensive set of model codes used in the us and abroad to help ensure the engineering of safe sustainable affordable and resilient structures.
Where standby power is connected to elevators the machine room ventilation or air conditioning shall be connected to the standby power source.
The area of vents in the hoistway or the elevator machine room and the smoke hole shall be not less than 3 1 2 percent of the area of the hoistway nor less than 3 square feet 0 28 m 2 for each elevator car whichever is greater.
This room normally houses the elevators machines controllers governors and related electrical.
G work space required in machine rooms and machinery spaces.
For example in california the ventilation system must keep the temperature below 104 degrees fahrenheit at all times.
The room environment is also subject to regulations.
Previously 524 cmr amended asme section 2 1 4 and required natural or mechanical ventilation for all enclosed hoistways and.
Requirements for elevator in readiness shall be as defined in sections 3003 3 1 through 3003 3 2.